Distribution Series 3 Dual Bus

The Distribution Series 3 from ICT is a dual-bus DC distribution panel designed to be used in 12-, 24- or 48-volt DC applications.  This dual-bus panel can support dual-voltage inputs and mixed polarities and is available with either fuse- or circuit breaker-protected outputs.  Models include a secure, easy-to-use web-browser interface, which provides remote power monitoring, power control, and alarm reporting over an Ethernet link, along with SNMP support for integration into your network management system.

Features

  • Supports +12, +24, and +/-48 volts DC applications
  • 200-amp peak system current / 180 amps continuous
  • Dual-bus architecture (Bus A & Bus B)
  • Total of 12 fused or breaker output positions rated up to 25 amps (12 & 24 V) and 20 amps (48 V) per output
  • 6 outputs per bus
  • Front-mounted fuses or breakers
  • Standard TCP/IP Ethernet communications provides full remote monitoring and control capabilities
  • Network security protocols include HTTPS, TLS 1.2, SNMP v1/v2c/v3
  • Reporting of total system current (Bus A & Bus B), individual load current, Bus A and Bus B system voltage, and fuse or breaker status
  • Alarm reporting via text or email notification
  • Remote individual output power toggling
  • Automatic load shedding disconnects non-critical loads when on battery power (user defined)
  • Network watchdog automatically reboots routers or switches when no response is received
  • Five digital site monitoring input contacts
  • Up to 30 days of data logging
  • Heavy duty input stud connectors
  • Form C alarm contacts
  • 1RU 19-inch rackmount form factor
  • Two-year warranty

Benefits

  • Full remote monitoring and power control reduces site visits, lowering total cost of ownership and maintenance costs
  • Improve the quality of service and uptime of your network by quickly resolving power issues remotely
  • Increase battery backup time with automatic load shedding by allowing non-critical loads to be removed from the system, maintaining critical loads for longer
  • No additional software required as monitoring and control is provided via an onboard web-based server
  • Support mixed-voltage sites with dual-bus architecture

Description

Power Specifications ICT200DF-12 ICT200DB-12 ICT200DF-12IRC ICT200DB-12IRC
Application Voltage (pos or neg gnd) 12, 24, 48VDC 12, 24, 48VDC 12, 24, 48VDC 12, 24, 48VDC
System Current Rating (peak/cont) 200A/160A 200A/160A 200A/160A 200A/160A
Bus current Rating (peak/cont) 100A/80A 100A/80A 100A/80A 100A/80A
Number of Outputs per bus 6 6 6 6
Operating Voltage Range 10-60VDC 10-60VDC 10-60VDC 10-60VDC
Number of ATO Fused DC Outputs 12 —- 12 —-
ATO Max Fuse Rating (12, 24V) 25A —- 25A —-
ATO Max Fuse Rating (48V) 25A —- 20A —-
Number of Breaker Outputs —- 12 —- 12
Max Breaker Outputs (12, 24V) —- 30A —- 30A
Max Breaker Outputs (48V) —- 30A —- 20A
Form Factor 1RU – 19 inch rack mount with handles
Dimensions (L x W x H) 9.29 x 19.0 x 1.72 Inches
Weight 7.0 lbs / 3.2 kg
Connectors M8 DC Input stud connectors, 10-22AWG cage clamp output terminal blocks
Operating Temperature Range -30°C to +60°C
CE, ROHS
Ethernet TCP/IP built-in web server and graphical user interface; 10/100 BASE-T; IEEE 802.3 compatible
Supported Protocols IPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMP v1/v2c/v3
SNMP Ports UDP Port 161, SNMP Traps: UDP Port 162
Firmware Upgrades Upgradable over Ethernet
Security Password protected, HTTPS, TLS 1.0
12 Channel Output Monitoring Current draw measured and reported for each output, definable under and over current alarms
Email and SMS Alerts Multiple email and text accounts with adjustable intervals
Data Logging Up to 30 days at one-minute sampling rate, CSV file download, major event logging
Network Watchdog Autonomously ping up to two I.P addresses and power-cycle output if no response, definable settings
Power Cycling and Rebooting Remote on/off control of every output individually
Auto Restore Mode Will return to previous output settings after a power loss
Power-up Delay Sequencing User selectable 0 to 60 seconds delay between outputs energizing
Auto Load Shedding Each output user definable, manual or auto restart
Remote Alarms Each output user definable, manual or auto restart