Hybrid Ultra

The ICT Hybrid Ultra combines a 48 or 24 volt DC power system with a factory installed 12 or 24 volt DC converter module to provide up to 7,500 watts of maximum power for a flexible hybrid DC solution for wireless network sites. The Hybrid Ultra accepts up to five hot swappable 48 or 24 volt, 1500-, 1000-, or 700-watt DC Power Modules. The integrated DC converter provides up to 700 watts of 12 or 24 volts DC output through a separate output bus bar.

FEATURES

  • Up to five 1500-, 1000-, or 700-watt, 48- or 24-volt DC system power modules
  • Total maximum total output power 7,500 watts
  • Integrated 700-watt 12-or 24-volt DC power converter
  • Dual 100-amp battery disconnect breakers
  • Integrated 150-amp low voltage disconnect with adjustable setpoints
  • Four or eight fully managed load distribution outputs (25 A max. each)
  • 90 to 95% efficiency
  • –30°C to +60°C operating temperature range
  • Standard TCP/IP Ethernet communications provides full remote monitoring and control capabilities
  • Network security protocols include HTTPS, TLS 1.3, SNMP v1/v2c/v3
  • User adjustable output voltages and battery charge current limit
  • Advanced battery management features including state of charge, estimated run-time remaining, battery discharge testing, temperature compensated charging
  • Alarm reporting via text or email notification
  • Battery temperature and site monitoring input contacts
  • 2RU 19-inch rackmount form factor
  • Support for lead-acid and lithium-ion battery types
  • Two-year warranty

 

BENEFITS

  • Configurable DC power system provides flexibility and scalability to meet application requirements
  • Integrated 700-watt DC-DC power module provides a secondary voltage for sites with mixed voltages requirements – 48 & 24 or 48 & 12 VDC
  • Reduce total cost of ownership by reducing site visits and maintenance costs due to remote monitoring and control functionality
  • Improve the quality of service and uptime of your network by quickly resolving power issues remotely
  • User-scheduled battery testing proactively alerts users when a connected backup battery is not holding charge
  • Real-time reporting on battery state of charge, battery run-time remaining, and battery voltage levels
  • Remotely monitor and toggle power to individually connected load devices utilizing load distribution module
  • All connection points are external, allowing for quick and easy installation
  • No additional software required as monitoring and control is provided via an onboard web-based server

 

Description

AC Input

Nominal System Voltage 120/240/VAC
Input Voltage Range 100-300-VAC
Power Factor (typical) 0.99
Frequency 50/60Hz


1,500W Power Modules

Model Number ICT1500-48PM ICT1500-24PM
Nominal Voltage 48 24
Output Voltage Range (adjustable) 46.0 – 62.0 VDC 23.0 -31.0 VDC
Output Current per Module (230VAC nom.) 27A 54A
Output Current per Module (115VAC nom.) 16A 32A
Power Factor 0.99 typ. 0.99 typ.
Efficiency (typical) 95% 94%
Output Ripple (rms) 60mV 40mV


1000W Power Modules

Model Number ICT1000-48PM
Nominal Voltage 48
Output Voltage Range (adjustable) 46.0 – 60.0 VDC
Output Current per Module 18A
Power Factor 0.99 typ.
Efficiency (typical) 91%
Output Ripple (rms) <60mV


700W Power Modules

Model Number ICT700-24PM ICT700-12PM
Nominal Voltage 24 12
Output Voltage Range (adjustable) 23.0 -31.0 VDC 11.5 – 15.5 VDC
Output Current per Module 25A 50A
Power Factor 0.99 typ. 0.99 typ.
Efficiency (typical) 91% 90%
Output Ripple (rms) 30mV 30mV

 

DC Converter

Power Output 700W 700W
Nominal Voltage 13.8 27.6
Output Voltage Range (adjustable) 11.5 – 15.5 VDC 23.0 – 31.0 VDC
Output Current per Module 50A 25A
Power Factor 0.99 typ. 0.99 typ.
Efficiency (typical) 92% 92%
Output Ripple (rms) 20mV 30mV
AC Input Connectors (dual) Terminal Block, #8 – #16 AWG
DC Output Connector Busbars with 1/4-20 x 7/8” bolts
Ethernet Connector RJ-45
Remote Alarm Connectors Terminal Block (#16 – 24 AWG)
Mounting 2RU, 19 inch rack mount
Weight (exc. Power Modules) 30lbs / 13.6 kg
Dimensions – H x W x L 3.5 x 19.0 x 15.7 in.

89 x 483 x 398 mm

Operating Temperature Range -30°C to +60°C
Output Derating 2% / °C (above 50° C)
Storage Temperature -45° to +85° C
Safety EN 60950-1
Emissions (48/24V only) EN61000-6-1. EN61000-6-3. EN61000-3-2, RoHS, CE
Load Outputs 12 or 8
Over Current Protection Hydraulic/magnetic circuit breakers
Max. Breaker Size 30A
Front Display High resolution OLED with function keys
Remote Communications TCP/IP 10/100 Base-T
I.P. Protocols HTTP/HTTPS, SMTP, SNMPv1/v2/v3
Inputs 4 digital, 1 analog temp sensor contacts
Battery Circuit Breaker Dual 100A
Low Voltage Disconnect 150A contactor
Two year warranty
Hybrid Ultra Data Sheet (pdf, 9314KB)
800-351-007
Hybrid Ultra Quick Start Guide (pdf, 470KB)
855-350-950_rev. 1.02
Hybrid Ultra Instruction Manual (pdf, 2841KB)