MPS Ultra 2

The next generation 2RU MPS Ultra 2 DC power system from ICT provides N+1 redundancy with 700-, 1000-, or 1500-watt hot-swappable DC power modules, providing up to 12,000 watts of power in 48-, 24-, or 12-volt models. With 10/100/1000 BASE-T Ethernet-based remote monitoring and DC power control; advanced battery management features, including an RS485 MODBUS interface which communicates directly with supported lithium-ion battery management systems; integrated dual 100-amp battery breakers; and up to 12 fully managed load outputs which can be monitored and power-cycled remotely, the MPS Ultra 2 provides unmatched capability for demanding DC applications.

Features

  • Hot-swappable 700-, 1000- or 1500-watt power modules available in 48-, 24- or 12-volt outputs provides up to 12,000 watts of output power in a 2U package
  • Available in four configurations to accommodate either four, five, seven, or eight power modules, integrated with battery management and load distribution modules
  • Integrated 10/100/1000 BASE-T TCP/IP Ethernet communications for remote power monitoring and control
  • Integrated RS485 MODBUS port for direct communication with supported lithium-ion battery management systems
  • Network security protocols include HTTPS, TLS 1.3, SNMP v1/v2c/v3
  • Battery Management Module includes dual 100-amp battery breakers and low voltage disconnect relay, with features including battery state-of-charge reporting, runtime remaining, equalization charging and battery discharge testing
  • Load Distribution Module available with four fully managed outputs (up to 12 managed outputs available)
  • Alarm reporting via text or email notification
  • Support for lead-acid and lithium-ion battery types
  • Two-year warranty

Benefits

  • Configurable DC power system provides flexibility and scalability to meet application requirements
  • Reduce total cost of ownership by reducing site visits and maintenance costs due to remote monitoring and control functionality
  • Improve the quality of service and up-time of your network by quickly resolving power issues remotely
  • User-scheduled battery testing proactively alerts users when a connected backup battery is not holding charge, allowing preemptive replacement, and ensuring reliable network backup upon AC power loss
  • Real-time reporting on battery state of charge, battery run-time remaining, and battery voltage levels
  • Remotely monitor and toggle power to individually connected load devices avoids unnecessary site visits
  • All connection points are external, allowing for quick and easy installation
  • No additional software required as monitoring and control is provided via an onboard web-base server

Description

AC Input

Nominal System Voltage 120/240/VAC
Input Voltage Range 100-300-VAC
Power Factor (typical) 0.99
Frequency 50/60Hz
 


1,500W Power Modules

Model Number ICT1500-48PM ICT1500-24PM
Nominal Voltage 48 24
Output Voltage Range (adjustable) 46.0 – 62.0 VDC 23.0 -31.0 VDC
Output Current per Module (230VAC nom.) 27A 54A
Output Current per Module (115VAC nom.) 16A 32A
Power Factor 0.99 typ. 0.99 typ.
Efficiency (typical) 95% 94%
Output Ripple (rms) 60mV 40mV


1000W Power Modules

Model Number ICT1000-48PM
Nominal Voltage 48
Output Voltage Range (adjustable) 46.0 – 60.0 VDC
Output Current per Module 18A
Power Factor 0.99 typ.
Efficiency (typical) 91%
Output Ripple (rms) <60mV


700W Power Modules

Model Number ICT700-24PM ICT700-12PM
Nominal Voltage 24 12
Output Voltage Range (adjustable) 23.0 -31.0 VDC 11.5 – 15.5 VDC
Output Current per Module 25A 50A
Power Factor 0.99 typ. 0.99 typ.
Efficiency (typical) 91% 90%
Output Ripple (rms) 30mV 30mV
AC Input Connectors (dual) 3-pin removable plug, cage clamp type 8–22 AWG
DC Output Connector Bus Bar, 5/16-inch bolt hole
Ethernet Connector RJ-45
Alarm Output Connector 3-pin removable plug, cage clamp type 16–24 AWG
Mounting 2RU, 19 inch rack mount
Weight (exc. Power Modules) 30lbs / 13.6 kg
Dimensions – H x W x L 3.5 x 19.0 x 16.3 inches

89 x 483 x 414 mm

Operating Temperature Range -30°C to +60°C
Output Derating 2% / °C (above 50° C)
Storage Temperature -45° to +85° C
Safety UL/CSA 62368-1
Emissions (48/24V only) ICES-003, FCC Part 15/B, EN 61000-6-2, EN 61000-6-3, EIC 61000-4-5, CE, RCM and RoHS (700 W)  |  ICES-003, FCC Part 15/B, EN 61000-6-1, EN 61000-6-3, EIC 61000-3-2, EIC 61000-3-3, CE, RCM and RoHS (1000 W)  |  ICES-003, EN55032, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-5, CE, RCM and RoHS (1500 W)
Load Outputs 12 or 8
Over Current Protection Hydraulic/magnetic circuit breakers
Max. Breaker Size 30A
Front Display High-resolution OLED with function keys
Remote Communications TCP/IP Ethernet 10/100/1000 BASE-T
Battery Communications RS-485 MODBUS to connect to battery BMS
I.P. Protocols HTTP/HTTPS, SMTP, SNMPv1/v2/v3
Inputs 4 digital, 1 analog temp sensor contacts
Battery Circuit Breaker Dual 100A
Low Voltage Disconnect 150A contactor
Two year warranty
MPS Ultra 2 Data Sheet (pdf, 457KB)
800-347-101
MPS Ultra 2 Quick Start Guide (pdf, 539KB)
855-347-950 Rev1.02
MPS Ultra 2 Instruction Manual (pdf, 3420KB)
855-347-050 rev. 1.05

Title